Kilian Cavalotti 657b17570a Add genpdu pdutype for generic SNMP PDUs (PDU2-MIB)
Add a new pdutype (genpdu) for PDUs implementing the Raritan PDU2-MIB.
A single MIB covers the Raritan PX2/PX3/PX4/PXC/SRC/PXO/BCM series, the
Server Technology PRO3X/PRO4X series, the Legrand intelligent PDUs, and
all PDUs following the PDU2-MIB.

Supports rpower (whole-PDU and per-outlet), rinv and rvitals over SNMP
v1, v2c or v3, with credentials read from the pdu table).

Unlike the existing types, sensor units and decimal precision are read
from the MIB per sensor rather than hardcoded, so readings are correct
across models that report differing precision for the same sensor.
Outlet switching capability is probed at connect time, so metered-only
models report a single "unsupported" message instead of a per-outlet error.

rspconfig is not supported for genpdu; PDU linking and BCM2/PMC power
meters are out of scope.

Tested on Raritan PX4-5851-E7V2 (fw 4.2.10.5-50400, switched),
PX3-1901U-N1 and PX3-1901U-N1A6 (fw 4.0.20.5-49038, metered), and
PX2-1901U-N1A6 (fw 4.0.20.5-49038, metered).

Signed-off-by: Kilian Cavalotti <kilian@stanford.edu>
2026-08-20 18:51:02 -07:00

165 lines
7.3 KiB
ReStructuredText

Generic SNMP PDU
================
The generic SNMP PDU support (``pdutype=genpdu``) drives any PDU that implements the Raritan **PDU2-MIB**. A single MIB covers the Raritan PX2, PX3, PX4, PXC, SRC, PXO and BCM series, the Server Technology PRO3X and PRO4X series, and the Legrand intelligent PDUs, so the same code path applies to all of them without per-model configuration.
xCAT communicates with these PDUs over SNMP v1, v2c or v3, using the credentials in the ``pdu`` table. Unlike the other PDU types, the sensor scaling factors and units are read from the device rather than hardcoded, so readings are correct on any model regardless of the precision it reports.
Defining a PDU
--------------
Create the PDU node definition and set the SNMP credentials in the ``pdu`` table.
For SNMP v2c: ::
mkdef mypdu groups=pdu nodetype=pdu mgt=pdu pdutype=genpdu
chdef mypdu snmpversion=2 community=<community>
For SNMP v3: ::
mkdef mypdu groups=pdu nodetype=pdu mgt=pdu pdutype=genpdu
chdef mypdu snmpversion=3 snmpuser=<user> \
authtype=SHA authkey=<passphrase> \
privtype=AES privkey=<passphrase> seclevel=authPriv
The ``seclevel`` attribute is optional. When it is not set, ``authPriv`` is used if ``privtype`` is set and ``authNoPriv`` otherwise. When ``privkey`` is not set it falls back to ``authkey``. If ``authtype`` or ``privtype`` are not set they default to ``SHA`` and ``DES``.
The ``outlet`` attribute is discovered automatically from the MIB on first use and cached in the ``pdu`` table. It can also be set explicitly to skip the discovery query.
Switched and metered PDUs
-------------------------
PDU2-MIB covers both switched models and metered-only models. xCAT detects which it is talking to at connection time, so no configuration is needed to distinguish them.
On a metered-only PDU, ``rinv`` and ``rvitals`` work normally, and the power control commands report that switching is unavailable rather than failing per outlet: ::
# rpower mypdu stat
mypdu: this PDU does not support outlet switching
Writing to a switched PDU requires credentials with write access. SNMP agents on these devices commonly grant read-only access by default, in which case xCAT reports ``noAccess`` on power commands while read commands continue to work. Configure a read-write community, or an SNMP v3 user with write permission, on the PDU itself.
PDU Commands
------------
Administrators will need to know the exact mapping of the outlets to each server in the frame. xCAT cannot validate the physical cable is connected to the correct server.
Add a ``pdu`` attribute to the compute node definition in the form "PDU_Name:outlet": ::
#
# Compute server cn01 has two power supplies
# connected to outlet 6 and 7 on pdu=mypdu
#
chdef cn01 pdu=mypdu:6,mypdu:7
The following commands are supported against a compute node:
* Check the pdu status for a compute node: ::
# rpower cn01 pdustat
cn01: mypdu operational state for outlet 6 is on
cn01: mypdu operational state for outlet 7 is on
* Power off the PDU outlets for a compute node: ::
# rpower cn01 pduoff
cn01: mypdu operational state for outlet 6 is off
cn01: mypdu operational state for outlet 7 is off
* Power on the PDU outlets for a compute node: ::
# rpower cn01 pduon
cn01: mypdu operational state for outlet 6 is on
cn01: mypdu operational state for outlet 7 is on
* Power cycling the PDU outlets for a compute node: ::
# rpower cn01 pdureset
cn01: mypdu operational state for outlet 6 is reset
cn01: mypdu operational state for outlet 7 is reset
The following commands are supported against a PDU:
* Check the status of the full PDU: ::
# rpower mypdu stat
mypdu: operational state for the outlet 1 is on
mypdu: operational state for the outlet 2 is on
mypdu: operational state for the outlet 3 is on
* Power off, on or reset the full PDU: ::
# rpower mypdu off
# rpower mypdu on
# rpower mypdu reset
* PDU inventory information: ::
# rinv mypdu
mypdu: PDU Manufacturer: Raritan
mypdu: PDU Model: PX4-5851-E7V2
mypdu: PDU Serial Number: XXXXXXXXXX
mypdu: PDU Rated Voltage: 360-415V
mypdu: PDU Rated Current: 24A
mypdu: PDU Rated Frequency: 50/60Hz
mypdu: PDU Rated VA: 15.0-17.3kVA
mypdu: PDU Inlet Count: 1
mypdu: PDU Overcurrent Protector Count: 6
mypdu: PDU Outlet Count: 36
mypdu: PDU Description: Raritan PDU, MD:PX4-5851-E7V2 HW:0x1D FW:4.2.10.5-50400
* PDU and outlet power information: ::
# rvitals mypdu
mypdu: inlet 1 RMS Voltage: 412 V
mypdu: inlet 1 RMS Current: 13.959 A
mypdu: inlet 1 Active Power: 8879 W
mypdu: inlet 1 Apparent Power: 8950 VA
mypdu: inlet 1 Power Factor: 0.99
mypdu: inlet 1 Frequency: 60.0 Hz
mypdu: inlet 1 Unbalanced Current: 11 %
mypdu: inlet 1 Reactive Power: 0 var
mypdu: inlet 1 Active Energy: 145702407 Wh
mypdu: inlet 1 Apparent Energy: 147093631 VAh
mypdu: outlet 1 RMS Current: 0.000 A
mypdu: outlet 1 Active Power: 0 W
mypdu: outlet 1 Active Energy: 0 Wh
mypdu: outlet 2 RMS Current: 2.793 A
mypdu: outlet 2 Active Power: 660 W
mypdu: outlet 2 Active Energy: 9794434 Wh
Units and decimal precision are read from the MIB for each sensor rather
than being hardcoded, so readings are correct on any model without
per-model configuration. The same sensor can therefore be reported at
different precision on different models: for example inlet RMS current
appears as ``13.959 A`` on a PX4 and ``18.1 A`` on a PX2, because the two
devices declare a different number of decimal digits for it.
Sensors that the device does not report are omitted, so the exact set of
lines varies by model. Per-outlet sensors are skipped entirely on models
that do not meter individual outlets. The reported sensor types are a
fixed list in the plugin and can be extended by adding entries to it;
types with no name defined are reported as ``sensor <N>``.
**Note:** ``rspconfig`` is not supported for ``pdutype=genpdu``. Network and hostname configuration should be done on the PDU itself.
**Note:** For BMC based compute nodes, turning the PDU outlet power on does not automatically power on the compute side. Users will need to issue ``rpower <node> on`` to power on the compute side after the BMC boots.
Limitations
-----------
* PDU linking (cascading multiple PDUs behind one management interface) is not supported. The MIB indexes outlets by link ID, and xCAT assumes the value used by unlinked units. BCM2 and PMC power meters are also out of scope for the same reason.
* ``authtype``, ``privtype`` and the other SNMP attributes are per-PDU attributes in the ``pdu`` table, so PDUs using different SNMP protocols need their values set individually.
Tested hardware
---------------
* Raritan PX4-5851-E7V2, firmware 4.2.10.5-50400 (switched, 36 outlets)
* Raritan PX3-1901U-N1 and PX3-1901U-N1A6, firmware 4.0.20.5-49038 (metered, 48 outlets)
* Raritan PX2-1901U-N1A6, firmware 4.0.20.5-49038 (metered, 48 outlets)