genpdu read negative-capable sensors from the unsigned value column, which the MIB leaves undefined for them: a PX4 answers it with 0 for inlet reactive power and carries the reading in the signed column. Use SensorSignedMinimum to pick the column, as the MIB specifies. The unsigned column is still needed for active energy, whose range exceeds Integer32 and reads 0 in the signed one. An unreachable PDU or a wrong credential looked like a PDU without switched outlets, since the switching probe was the first exchange with the device. Probe pduCount first (implemented by every PDU2 agent, verified on PX2, PX3 and PX4) and return no session when it fails, so callers print "Couldn't connect to <pdu>". Warn when pduCount is not 1 rather than refusing: a linked primary still answers for its own outlets. Add unit tests for the genpdu sensor, session and inventory paths. Signed-off-by: Kilian Cavalotti <kilian@stanford.edu>
171 lines
7.8 KiB
ReStructuredText
171 lines
7.8 KiB
ReStructuredText
Generic SNMP PDU
|
|
================
|
|
|
|
The generic SNMP PDU support (``pdutype=genpdu``) drives any PDU that implements the Raritan **PDU2-MIB**. A single MIB covers the Raritan PX2, PX3, PX4, PXC, SRC, PXO and BCM series, the Server Technology PRO3X and PRO4X series, and the Legrand intelligent PDUs, so the same code path applies to all of them without per-model configuration.
|
|
|
|
xCAT communicates with these PDUs over SNMP v1, v2c or v3, using the credentials in the ``pdu`` table. Unlike the other PDU types, the sensor scaling factors and units are read from the device rather than hardcoded, so readings are correct on any model regardless of the precision it reports.
|
|
|
|
|
|
Defining a PDU
|
|
--------------
|
|
|
|
Create the PDU node definition and set the SNMP credentials in the ``pdu`` table.
|
|
|
|
For SNMP v2c: ::
|
|
|
|
mkdef mypdu groups=pdu nodetype=pdu mgt=pdu pdutype=genpdu
|
|
chdef mypdu snmpversion=2 community=<community>
|
|
|
|
For SNMP v3: ::
|
|
|
|
mkdef mypdu groups=pdu nodetype=pdu mgt=pdu pdutype=genpdu
|
|
chdef mypdu snmpversion=3 snmpuser=<user> \
|
|
authtype=SHA authkey=<passphrase> \
|
|
privtype=AES privkey=<passphrase> seclevel=authPriv
|
|
|
|
The ``seclevel`` attribute is optional. When it is not set, ``authPriv`` is used if ``privtype`` is set and ``authNoPriv`` otherwise. When ``privkey`` is not set it falls back to ``authkey``. If ``authtype`` or ``privtype`` are not set they default to ``SHA`` and ``DES``.
|
|
|
|
The ``outlet`` attribute is discovered automatically from the MIB on first use and cached in the ``pdu`` table. It can also be set explicitly to skip the discovery query.
|
|
|
|
|
|
Switched and metered PDUs
|
|
-------------------------
|
|
|
|
PDU2-MIB covers both switched models and metered-only models. xCAT detects which it is talking to at connection time, so no configuration is needed to distinguish them.
|
|
|
|
On a metered-only PDU, ``rinv`` and ``rvitals`` work normally, and the power control commands report that switching is unavailable rather than failing per outlet: ::
|
|
|
|
# rpower mypdu stat
|
|
mypdu: this PDU does not support outlet switching
|
|
|
|
Writing to a switched PDU requires credentials with write access. SNMP agents on these devices commonly grant read-only access by default, in which case xCAT reports ``noAccess`` on power commands while read commands continue to work. Configure a read-write community, or an SNMP v3 user with write permission, on the PDU itself.
|
|
|
|
|
|
PDU Commands
|
|
------------
|
|
|
|
Administrators will need to know the exact mapping of the outlets to each server in the frame. xCAT cannot validate the physical cable is connected to the correct server.
|
|
|
|
Add a ``pdu`` attribute to the compute node definition in the form "PDU_Name:outlet": ::
|
|
|
|
#
|
|
# Compute server cn01 has two power supplies
|
|
# connected to outlet 6 and 7 on pdu=mypdu
|
|
#
|
|
chdef cn01 pdu=mypdu:6,mypdu:7
|
|
|
|
The following commands are supported against a compute node:
|
|
|
|
* Check the pdu status for a compute node: ::
|
|
|
|
# rpower cn01 pdustat
|
|
cn01: mypdu operational state for outlet 6 is on
|
|
cn01: mypdu operational state for outlet 7 is on
|
|
|
|
* Power off the PDU outlets for a compute node: ::
|
|
|
|
# rpower cn01 pduoff
|
|
cn01: mypdu operational state for outlet 6 is off
|
|
cn01: mypdu operational state for outlet 7 is off
|
|
|
|
* Power on the PDU outlets for a compute node: ::
|
|
|
|
# rpower cn01 pduon
|
|
cn01: mypdu operational state for outlet 6 is on
|
|
cn01: mypdu operational state for outlet 7 is on
|
|
|
|
* Power cycling the PDU outlets for a compute node: ::
|
|
|
|
# rpower cn01 pdureset
|
|
cn01: mypdu operational state for outlet 6 is reset
|
|
cn01: mypdu operational state for outlet 7 is reset
|
|
|
|
The following commands are supported against a PDU:
|
|
|
|
* Check the status of the full PDU: ::
|
|
|
|
# rpower mypdu stat
|
|
mypdu: operational state for the outlet 1 is on
|
|
mypdu: operational state for the outlet 2 is on
|
|
mypdu: operational state for the outlet 3 is on
|
|
|
|
* Power off, on or reset the full PDU: ::
|
|
|
|
# rpower mypdu off
|
|
# rpower mypdu on
|
|
# rpower mypdu reset
|
|
|
|
* PDU inventory information: ::
|
|
|
|
# rinv mypdu
|
|
mypdu: PDU Manufacturer: Raritan
|
|
mypdu: PDU Model: PX4-5851-E7V2
|
|
mypdu: PDU Serial Number: XXXXXXXXXX
|
|
mypdu: PDU Rated Voltage: 360-415V
|
|
mypdu: PDU Rated Current: 24A
|
|
mypdu: PDU Rated Frequency: 50/60Hz
|
|
mypdu: PDU Rated VA: 15.0-17.3kVA
|
|
mypdu: PDU Inlet Count: 1
|
|
mypdu: PDU Overcurrent Protector Count: 6
|
|
mypdu: PDU Outlet Count: 36
|
|
mypdu: PDU Description: Raritan PDU, MD:PX4-5851-E7V2 HW:0x1D FW:4.2.10.5-50400
|
|
|
|
* PDU and outlet power information: ::
|
|
|
|
# rvitals mypdu
|
|
mypdu: inlet 1 RMS Voltage: 412 V
|
|
mypdu: inlet 1 RMS Current: 13.959 A
|
|
mypdu: inlet 1 Active Power: 8879 W
|
|
mypdu: inlet 1 Apparent Power: 8950 VA
|
|
mypdu: inlet 1 Power Factor: 0.99
|
|
mypdu: inlet 1 Frequency: 60.0 Hz
|
|
mypdu: inlet 1 Unbalanced Current: 11 %
|
|
mypdu: inlet 1 Reactive Power: -1360 var
|
|
mypdu: inlet 1 Active Energy: 145702407 Wh
|
|
mypdu: inlet 1 Apparent Energy: 147093631 VAh
|
|
mypdu: outlet 1 RMS Current: 0.000 A
|
|
mypdu: outlet 1 Active Power: 0 W
|
|
mypdu: outlet 1 Active Energy: 0 Wh
|
|
mypdu: outlet 2 RMS Current: 2.793 A
|
|
mypdu: outlet 2 Active Power: 660 W
|
|
mypdu: outlet 2 Active Energy: 9794434 Wh
|
|
|
|
Units and decimal precision are read from the MIB for each sensor rather
|
|
than being hardcoded, so readings are correct on any model without
|
|
per-model configuration. The same sensor can therefore be reported at
|
|
different precision on different models: for example inlet RMS current
|
|
appears as ``13.959 A`` on a PX4 and ``18.1 A`` on a PX2, because the two
|
|
devices declare a different number of decimal digits for it.
|
|
|
|
Sensors that can read negative, such as reactive power, are taken from the
|
|
signed value column of the MIB, which the device selects through the
|
|
sensor's signed minimum. The unsigned column is used for every other
|
|
sensor, including wide-range ones such as active energy, where the signed
|
|
column does not apply.
|
|
|
|
Sensors that the device does not report are omitted, so the exact set of
|
|
lines varies by model. Per-outlet sensors are skipped entirely on models
|
|
that do not meter individual outlets. The reported sensor types are a
|
|
fixed list in the plugin and can be extended by adding entries to it;
|
|
types with no name defined are reported as ``sensor <N>``.
|
|
|
|
**Note:** ``rspconfig`` is not supported for ``pdutype=genpdu``. Network and hostname configuration should be done on the PDU itself.
|
|
|
|
**Note:** For BMC based compute nodes, turning the PDU outlet power on does not automatically power on the compute side. Users will need to issue ``rpower <node> on`` to power on the compute side after the BMC boots.
|
|
|
|
|
|
Limitations
|
|
-----------
|
|
|
|
* PDU linking (cascading multiple PDUs behind one management interface) is not supported. The MIB indexes outlets by link ID, and xCAT assumes the value used by unlinked units, so only the primary unit is managed. BCM2 and PMC power meters are out of scope for the same reason. A PDU reporting more than one unit is not refused, but every command against it warns that only the primary unit is being driven.
|
|
|
|
* ``authtype``, ``privtype`` and the other SNMP attributes are per-PDU attributes in the ``pdu`` table, so PDUs using different SNMP protocols need their values set individually.
|
|
|
|
|
|
Tested hardware
|
|
---------------
|
|
|
|
* Raritan PX4-5851-E7V2, firmware 4.2.10.5-50400 (switched, 36 outlets)
|
|
* Raritan PX3-1901U-N1 and PX3-1901U-N1A6, firmware 4.0.20.5-49038 (metered, 48 outlets)
|
|
* Raritan PX2-1901U-N1A6, firmware 4.0.20.5-49038 (metered, 48 outlets)
|