Skip CPU temperatures from unbooted EUREKA node BMCs
A node whose BMC is not reporting returns Reading 0 from its temperature sensors, dragging averages down with meaningless values. The ComputerSystem Oem data flags this via HasBMCMetrics; skip such nodes, and keep collecting when the flag is absent.
This commit is contained in:
@@ -86,7 +86,9 @@ class OEMHandler(generic.OEMHandler):
|
||||
"""Read CPU temperatures from EUREKA BMC sensor endpoints.
|
||||
|
||||
Reads BMC{N}CPU0Temp and BMC{N}CPU1Temp sensors from
|
||||
/redfish/v1/Chassis/1/Sensors/.
|
||||
/redfish/v1/Chassis/1/Sensors/. Nodes whose BMC is not
|
||||
currently reporting (HasBMCMetrics false) are skipped, as
|
||||
their sensors read a meaningless 0.
|
||||
"""
|
||||
cputemps = []
|
||||
for sysurl in self._allsysurls:
|
||||
@@ -94,6 +96,13 @@ class OEMHandler(generic.OEMHandler):
|
||||
nodeid = nodeid.replace('Node', '')
|
||||
if not nodeid.isdigit():
|
||||
continue
|
||||
try:
|
||||
sysinfo = await fishclient._do_web_request(sysurl)
|
||||
except Exception:
|
||||
continue
|
||||
if not sysinfo.get('Oem', {}).get('Megware', {}).get(
|
||||
'HasBMCMetrics', True):
|
||||
continue
|
||||
for cpu in ('CPU0', 'CPU1'):
|
||||
try:
|
||||
sensor_url = '/redfish/v1/Chassis/1/Sensors/BMC{}{}Temp'.format(nodeid, cpu)
|
||||
|
||||